Rinnai · Boiler
310 Freeze protection thermistor fault
What the control is telling you
Fault detected in the freeze protection thermistor circuit.
Applies to: I-Series Plus boilers — 150K BTU and smaller and 175K BTU and higher (Combi and Solo)
Likely causes
- Loose, broken or damaged thermistor wiring/connectors
- Thermistor unplugged (reads -40)
- Damaged or failed thermistor
- Faulty PC Board
Test and repair steps
- Inspect the thermistor harness from the sensor back to the PC Board for loose, broken or damaged connections.
- Caution shut off the water supply and drain the system down before going further.
- Open Performance Data 05 and compare the displayed temperature with a thermometer at the same spot. Within 5° = sensor OK; more than 5° off = continue; a reading of -40 means unplugged or poor connection.
- Remove the thermistor and check it for damage.
- Disconnect and measure at the thermistor side on a 50K ohm range; resistance should drop when warmed by hand and rise against ice. 150K and smaller: CN7 pins 7 and 10. 175K and higher: CN7 pins 7 and 14.
- Compare readings against Appendix C Ambient Temperatures in the source manual (p.17 references it); replace the sensor if it is off by more than 5°F.
- Cross-check the readings with the controller's performance data; if correct, reinstall the thermistor.
- Fire the unit again; if code 310 persists, replace the thermistor.
- If the code returns after a new thermistor, replace the PC Board.
Models that show this code
6 models in I-Series Plus 150K and smaller, I-Series Plus 175K and higher
Other codes on the same units
- 180 Gas valve air/fuel adjustment limit reached
- 190 Electrical grounding / short in DC circuit
- 210 Data transfer error
- 220 Gas valve position not detected (reed switch)
- 250 Condensate pump switch tripped (accessory)
- 303 Secondary system thermistor fault
- 353 CH supply thermistor fault
- 363 CH return thermistor fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting I-Series Plus Boiler Diagnostic Codes (800000375), p.17. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.