NTI · Boiler

1 16 Floor thermostat contact open

Medium severity TRX

What the control is telling you

The floor safety thermostat contact is open. Auto reset.

Applies to: TRX150

Likely causes

  • Parameter 223 set to 0 with no floor thermostat fitted
  • Floor thermostat tripped because the CH setpoint is too high

Test and repair steps

  1. If parameter 223 is 0 and no floor safety thermostat is fitted, set parameter 223 to 1 or connect a floor safety thermostat.
  2. If parameter 223 is 0 and a floor safety thermostat is fitted, reduce the CH setpoint.

Models that show this code

5 models in TRX

TRX085TRX110CTRX150TRX199TRX199C

Other codes on the same units

  • 01 08 Low water pressure lockout (water pressure switch)
  • 1 10 CH flow temperature probe open or short circuit
  • 1 12 CH return temperature probe open or short circuit
  • 1 14 External (outdoor) sensor open or short circuit
  • 1 P1 Insufficient circulation or missing water (warning)
  • 1 P2 Insufficient circulation or missing water (warning)
  • 1 P3 Inadequate circulation or missing water (warning)
  • 02 01 Damaged or shorted DHW temperature probe

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: NTI TRX150 manual, p. 90. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.