NTI · Boiler
1 10 CH flow temperature probe open or short circuit
What the control is telling you
Clears when the CH temperature decreases.
Applies to: TRX150
Likely causes
- Loose or damaged sensor wiring
- Failed sensor
Test and repair steps
- Check the CH temperature sensor and make sure the connections are secure.
- Check the sensor resistance. If it is zero, replace the sensor.
- If the problem continues, replace the main control.
Models that show this code
5 models in TRX
Other codes on the same units
- 01 05 Insufficient circulation or low water pressure
- 01 06 Insufficient circulation or low water pressure
- 01 07 Insufficient circulation or water
- 01 08 Low water pressure lockout (water pressure switch)
- 1 12 CH return temperature probe open or short circuit
- 1 14 External (outdoor) sensor open or short circuit
- 1 16 Floor thermostat contact open
- 1 P1 Insufficient circulation or missing water (warning)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI TRX150 manual, p. 90. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.