NTI · Boiler
1 14 External (outdoor) sensor open or short circuit
What the control is telling you
Clears when the condition is fixed. While active, the boiler runs CH at a fixed setpoint equal to setting 4.0.2 (5.0.2 or 6.0.2 for zones 2 and 3).
Applies to: TRX150
Likely causes
- Damaged sensor wiring (staples can cut wires)
- Failed outdoor sensor
Test and repair steps
- Check the outdoor sensor and make sure all wiring is intact and secure.
- Check the outdoor sensor resistance against Table 37 (not on these pages). Replace the sensor if it does not match.
- If the problem continues, replace the outdoor sensor.
Models that show this code
5 models in TRX
Other codes on the same units
- 01 07 Insufficient circulation or water
- 01 08 Low water pressure lockout (water pressure switch)
- 1 10 CH flow temperature probe open or short circuit
- 1 12 CH return temperature probe open or short circuit
- 1 16 Floor thermostat contact open
- 1 P1 Insufficient circulation or missing water (warning)
- 1 P2 Insufficient circulation or missing water (warning)
- 1 P3 Inadequate circulation or missing water (warning)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI TRX150 manual, p. 90. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.