02 01 Damaged or shorted DHW temperature probe
What the control is telling you
Applies to Combi models only. The controller uses the boiler return sensor in place of the DHW outlet sensor and keeps running CH and DHW.
Applies to: TRX150 (Combi models)
Likely causes
- Damaged or shorted DHW outlet probe
- Loose wiring
Test and repair steps
- Check the DHW outlet temperature probe and wiring. Make sure the connections are secure.
- Check the sensor resistance against Table 37 (not on these pages). Replace the sensor if it does not match.
- If the problem continues, replace the main control.
Models that show this code
5 models in TRX
Other codes on the same units
- 1 16 Floor thermostat contact open
- 1 P1 Insufficient circulation or missing water (warning)
- 1 P2 Insufficient circulation or missing water (warning)
- 1 P3 Inadequate circulation or missing water (warning)
- 02 03 Storage temperature probe open or short circuit
- 02 05 DHW inlet probe open circuit
- 02 09 Storage overheating
- 2 P2 Anti-Legionella function not completely finished
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI TRX150 manual, p. 91. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.