NTI · Boiler

02 03 Storage temperature probe open or short circuit

Medium severity TRX

What the control is telling you

Applies to Non-Combi boilers with a DHW tank sensor. CH demand continues to run.

Applies to: TRX150 (Non-Combi with tank sensor)

Likely causes

  • Damaged tank sensor or wiring

Test and repair steps

  1. Check the tank sensor wiring.
  2. If no tank sensor is used, set parameter 2.2.8 to 2.

Models that show this code

5 models in TRX

TRX085TRX110CTRX150TRX199TRX199C

Other codes on the same units

  • 1 P1 Insufficient circulation or missing water (warning)
  • 1 P2 Insufficient circulation or missing water (warning)
  • 1 P3 Inadequate circulation or missing water (warning)
  • 02 01 Damaged or shorted DHW temperature probe
  • 02 05 DHW inlet probe open circuit
  • 02 09 Storage overheating
  • 2 P2 Anti-Legionella function not completely finished
  • 03 01 Display EEPROM error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: NTI TRX150 manual, p. 91. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.