Navien · Air conditioner
P9 Outdoor fan motor fault
What the control is telling you
The fan drive circuit on the outdoor board saw a problem with the DC fan motor.
Applies to: NAA17V36 (24K/36K), NAA17V60 (48K/60K)
Likely causes
- Supply voltage problem
- Failed DC fan motor
- PCB fan drive fault
Test and repair steps
- Check supply voltage (230 V).
- Check the PCB fan motor output for 310 VDC. Careful: live DC.
- 310 VDC is there replace the fan motor (power off first).
- No 310 VDC replace the outdoor PCB.
Models that show this code
2 models in Navien NAA
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAA Series Air Conditioner Service Manual, 3.2.16, p.40-41. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.