Navien · Air conditioner
P5 Condenser coil (T3) temperature too high - cooling
What the control is telling you
The T3 condenser sensor read over 140°F (60°C) in cooling, so the unit protects itself. Three P5 trips within 180 minutes turn into H1.
Applies to: Navien NAA17V36 / NAA17V60 R-454B outdoor units
Likely causes
- T3 sensor loose or off resistance
- Dirty or blocked outdoor coil, or blocked fan discharge
- Restriction on the low side: kinked line set, plugged filter-drier (can show as frosted suction, high discharge temp or low amps)
- Bad PCB
Test and repair steps
- Power off and wait at least 5 minutes before touching the inverter board.
- Check the T3 sensor plug and measure its resistance against the sensor table.
- Clean the outdoor coil and clear anything blocking the fan outlet.
- Look for kinks in the line set and a plugged filter-drier. Clear the restriction. If ice is the blockage, clean the system.
- If all checks pass, replace the PCB.
Models that show this code
2 models in Navien NAA
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAA Series Air Conditioner Service Manual V1.00 (March 2026), 3.1 Error Code Classification p.20; 3.2.13 P5 p.35. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.