Navien · Air conditioner

P6 Compressor drive (IPM) module protection

Critical severity Navien NAA

What the control is telling you

The compressor drive module on the outdoor board reported a fault.

Applies to: NAA17V36 (24K/36K), NAA17V60 (48K/60K)

Likely causes

  • Supply voltage not 230 V
  • Dirty or blocked outdoor coil
  • Air or nitrogen in the system
  • Thermal paste on the module dried out or uneven
  • Compressor winding problem
  • PCB fault

Test and repair steps

  1. Check supply voltage (230 V).
  2. Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
  3. Check the outdoor coil and airflow.
  4. Open the refrigerant cooling cover on the module and check the white thermal paste. Re-apply it if it is thin or patchy.
  5. Ohm the compressor U-V-W windings each pair should be within 20 Ω and every terminal to ground should read open (MΩ).
  6. Bad readings, or loud noise / high amps when running: replace the compressor. Recover the R-454B charge with A2L-rated equipment before opening the sealed system.
  7. Everything checks good replace the outdoor PCB.

Models that show this code

2 models in Navien NAA

NAA17V36NAA17V60

Other codes on the same units

  • L1 DC bus voltage too high
  • P1 High pressure switch opened
  • P2 Low pressure protection
  • P3 Compressor drive overcurrent
  • P4 Discharge temperature too high
  • P5 Condenser coil (T3) temperature too high - cooling
  • P8 Drive module (IPM) overheating
  • P9 Outdoor fan motor fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAA Series Air Conditioner Service Manual, 3.2.14, p.36-38. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.