Navien · Air conditioner
E999 Error of unknown cause
What the control is telling you
The controller locked out for a reason it could not identify. Manual reset needed. The manual gives no procedure for this code.
Applies to: NAE28V3622A1, NAE28V6022A1
Models that show this code
2 models in Navien NAE
Other codes on the same units
- E817 Inverter trip: DC over voltage
- E818 Inverter trip: AC under voltage
- E819 Inverter trip: AC over voltage
- E820 Inverter trip: PFC unbalanced current
- E821 Inverter trip: Fan motor error (5 min)
- E822 Inverter trip: Discharge FET error
- E823 Inverter trip: Stator overheat (5 min)
- E824 Inverter trip: PBA (power board) over temperature
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAE I&O manual (07/2026), 7.1 Error table, p.42. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.