Navien · Air conditioner
E822 Inverter trip: Discharge FET error
What the control is telling you
Inverter trip error shown after alarm 872 occurred four times. Manual reset needed (display shows 822).
Applies to: NAE28V3622A1, NAE28V6022A1
Likely causes
- FET damaged by heat, overcurrent or overvoltage
- Poor connection
- Abnormal current flow
- Aged components
Test and repair steps
- Turn off power at the disconnect before opening the unit.
- Check the circuit and wiring around the FET.
- Check FET temperature and condition.
- Recheck connections.
Models that show this code
2 models in Navien NAE
Other codes on the same units
- E817 Inverter trip: DC over voltage
- E818 Inverter trip: AC under voltage
- E819 Inverter trip: AC over voltage
- E820 Inverter trip: PFC unbalanced current
- E821 Inverter trip: Fan motor error (5 min)
- E823 Inverter trip: Stator overheat (5 min)
- E824 Inverter trip: PBA (power board) over temperature
- E999 Error of unknown cause
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAE I&O manual (07/2026), 7.1 Error table and 7.2.39, p.62. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.