E3 Remote controller cannot transmit
What the control is telling you
The remote could not find a free moment on the line for 6 seconds, or saw its own data come back different 30 times in a row.
Applies to: PEAD-RP35/50/60/71/100/125/140JA and JA(L) ducted indoor units (220-240 V models)
Likely causes
- Two remotes both set to Main
- Remote wired to more than one indoor unit
- Duplicate refrigerant address
- Faulty remote controller or indoor board
- Electrical noise on the remote wire
Test and repair steps
- Set one remote to Main and the other to Sub.
- Connect the remote to only one indoor unit per refrigerant system.
- Give each system its own refrigerant address.
- Run the remote self-diagnosis RC OK = cycle power, replace the indoor board if it returns; RC NG = replace the remote; RC E3 or ERC = noise, reroute the remote wire.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Mitsubishi Electric PEAD-RP35-140JA(L) Service Manual, 10-3 Self-diagnosis action table, p.33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.