Mitsubishi · Heat pump
E3 Remote controller cannot transmit
What the control is telling you
The remote could not find a free moment on the line for 6 seconds, or saw its own data come back different 30 times in a row.
Applies to: PEAD-RP35/50/60/71/100/125/140JA and JA(L) ducted indoor units (220-240 V models)
Likely causes
- Two remotes both set to Main
- Remote wired to more than one indoor unit
- Duplicate refrigerant address
- Faulty remote controller or indoor board
- Electrical noise on the remote wire
Test and repair steps
- Set one remote to Main and the other to Sub.
- Connect the remote to only one indoor unit per refrigerant system.
- Give each system its own refrigerant address.
- Run the remote self-diagnosis RC OK = cycle power, replace the indoor board if it returns; RC NG = replace the remote; RC E3 or ERC = noise, reroute the remote wire.
Models that show this code
14 models in Mr. Slim PEAD-RP JA(L) ducted indoor unit
Other codes on the same units
- E0 Remote controller not receiving from indoor unit
- E1 Remote controller memory error
- E2 Remote controller clock error
- E4 Indoor unit not receiving from remote controller
- E5 Indoor unit cannot transmit to remote controller
- E6 Indoor/outdoor communication - indoor not receiving
- E7 Indoor unit transmit error to outdoor unit
- LED1 (indoor board) Indoor board LED1 - control power
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Mitsubishi Electric PEAD-RP35-140JA(L) Service Manual, 10-3 Self-diagnosis action table, p.33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.