Mitsubishi · Heat pump
E0 Remote controller not receiving from indoor unit
What the control is telling you
The main or sub remote has received nothing valid from the address-0 indoor unit for 3 minutes, or a sub remote has received nothing for 2 minutes.
Applies to: PEAD-RP35/50/60/71/100/125/140JA and JA(L) ducted indoor units (220-240 V models)
Likely causes
- Remote controller wire loose or broken
- Both remote controllers set to Sub (none set to Main)
- Remote controller wired wrong, or wired to more than one indoor unit
- Refrigerant address repeated in a group
- Faulty remote controller
- Faulty indoor control board (address 0 unit)
- Electrical noise on the remote controller wire
Test and repair steps
- Check the remote controller wire at the remote and at the indoor terminal block for loose or broken connections.
- With two remotes, set one to Main and the other to Sub.
- Wiring limits total length 500 m max, up to 16 indoor units and 2 remotes per group; do not use multi-core cable with 3 or more cores.
- Run the remote controller self-diagnosis RC OK = remote is fine, cycle power and replace the indoor board if the code returns; RC NG = replace the remote; RC E3 or ERC = noise on the line - reroute the wire away from power cables.
- In group control, if a new indoor board does not fix it, check the board in the unit with refrigerant address 0.
Models that show this code
14 models in Mr. Slim PEAD-RP JA(L) ducted indoor unit
Other codes on the same units
- E1 Remote controller memory error
- E2 Remote controller clock error
- E3 Remote controller cannot transmit
- E4 Indoor unit not receiving from remote controller
- E5 Indoor unit cannot transmit to remote controller
- E6 Indoor/outdoor communication - indoor not receiving
- E7 Indoor unit transmit error to outdoor unit
- LED1 (indoor board) Indoor board LED1 - control power
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Mitsubishi Electric PEAD-RP35-140JA(L) Service Manual, 10-3 Self-diagnosis action table, p.33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.