Mitsubishi · Heat pump
E6 Indoor/outdoor communication - indoor not receiving
What the control is telling you
The indoor board has not received a valid signal from the outdoor unit for 6 minutes after power-up, or for 3 minutes during operation. On twin/triple systems, also set when the indoor board does not get the outdoor board's permission-to-send signal for 3 minutes.
Applies to: PEAD-RP35/50/60/71/100/125/140JA and JA(L) ducted indoor units (220-240 V models)
Likely causes
- S1/S2/S3 indoor-outdoor wire loose, shorted or crossed
- Faulty send/receive circuit on the indoor board
- Faulty send/receive circuit on the outdoor board
- Electrical noise on the indoor/outdoor wire
Test and repair steps
- Turn the unit off at the remote first, then switch off the breaker before opening the unit or unplugging connectors.
- Check the S1, S2 and S3 connections at both terminal blocks for looseness, damage or reversed wires. On twin/triple systems, check every unit.
- If you have the A-Control service tool (PAC-SK52ST), read the LED code on the outdoor board; if it shows EA-EC, follow that code first.
- Cycle power. If the code returns, replace the indoor or outdoor control board.
- On twin/triple systems another indoor board may be the faulty one.
Models that show this code
14 models in Mr. Slim PEAD-RP JA(L) ducted indoor unit
Other codes on the same units
- E2 Remote controller clock error
- E3 Remote controller cannot transmit
- E4 Indoor unit not receiving from remote controller
- E5 Indoor unit cannot transmit to remote controller
- E7 Indoor unit transmit error to outdoor unit
- LED1 (indoor board) Indoor board LED1 - control power
- LED2 (indoor board) Indoor board LED2 - remote controller power
- LED3 (indoor board) Indoor board LED3 - indoor/outdoor communication
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Mitsubishi Electric PEAD-RP35-140JA(L) Service Manual, 10-3 Self-diagnosis action table, p.34. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.