Kinghome · Heat pump
SW1 Outdoor board debug menu (SW1 held 5 s)
What the display is showing
On the KU cold-climate outdoor unit, holding SW1 for about 5 seconds opens a first-level debug menu and the outdoor board display starts flashing. Short presses of SW1 step through the menu items. The manual describes item 06 (forced defrost), 08 (refrigerant recovery) and 09 (forced operation). With no key press for 10 seconds the menu closes.
Applies to: Kinghome Ultranixx cold-climate KU36UHO and KU60UHO outdoor units with KU..UH2I and KD..UHI air handlers
What to do
- Hold SW1 about 5 seconds until the board display flashes.
- Short-press SW1 to move to the item you need (06, 08 or 09).
- Use SW2 or SW3 to change the value, then short-press SW1 to save.
- Leave it alone for 10 seconds to exit.
Models that show this code
6 models in Kinghome Ultranixx
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Kinghome Ultranixx cold-climate KU36/60UHO service manual GC202306, sec. 2.3.5 to 2.3.7. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.