Kinghome · Heat pump
P8 Power module over-temperature
What the control is telling you
The power module temperature exceeded its limit.
Applies to: Kinghome KM09HT1DI, KM12HT1DI, KM18HT1DI, KM24HT1DI wall mini-splits; Kinghome KM09HF1DI to KM24HF1DI wall mini-splits (Gree GFH..DA/DB); Kinghome Ultranixx cold-climate KU36UHO and KU60UHO outdoor units with KU..UH2I and KD..UHI air handlers
Likely causes
- Thermal grease missing or uneven
- Module screws loose
- Faulty temperature sampling
Test and repair steps
- De-energize and wait 20 min.
- Check thermal grease and the heat-sink fit.
- Retighten module screws.
- Replace the board if needed.
Models that show this code
15 models in Kinghome KM HT1DI, Kinghome KM HF1DI, Kinghome Ultranixx
Other codes on the same units
- P3 Compressor intermediate-frequency test display
- P5 Compressor phase overcurrent
- P6 Main-to-driver communication error
- P7 Module temperature sensor circuit fault
- SW1 Outdoor board debug menu (SW1 held 5 s)
- U1 Compressor phase current detection circuit fault
- U3 DC bus voltage drop fault
- U5 Whole-unit current detection fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Kinghome KM09-12-18-24HT1DI service manual, sec. 9.1 error code list; Kinghome KM09-24HF1DI service manual, sec. 11.1 error code list; Kinghome Ultranixx cold-climate KU36/60UHO service manual GC202306, sec. 3.3-3.4. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.