Kinghome · Heat pump

+ - + - + - Forced defrost request (remote key sequence)

Menu / mode display Kinghome KM HEDIKinghome KM HT1DI

What the display is showing

A service key sequence on the remote that forces the system into a defrost cycle. While it runs the heating lamp shows the defrost pattern (on 10 s, off 0.5 s). The indoor unit leaves the forced-defrost setting when the outdoor unit reports back, and the unit then returns to normal heating. If a fault or protection stop is active the sequence only works after that clears.

Applies to: Kinghome KM09HEDI, KM12HEDI, KM18HEDI wall mini-splits; Kinghome KM09HT1DI, KM12HT1DI, KM18HT1DI, KM24HT1DI wall mini-splits

What to do

  1. Turn the unit on in heating mode and set 16°C.
  2. Within 5 seconds press + - + - + - on the remote.
  3. The unit exits the forced defrost by itself when the outdoor unit finishes.

Models that show this code

7 models in Kinghome KM HEDI, Kinghome KM HT1DI

KM09HEDIKM09HT1DIKM12HEDIKM12HT1DIKM18HEDIKM18HT1DIKM24HT1DI

Other codes on the same units

  • P8 Power module over-temperature
  • U1 Compressor phase current detection circuit fault
  • U3 DC bus voltage drop fault
  • U5 Whole-unit current detection fault
  • U7 Four-way valve abnormal
  • Cool lamp Cool lamp lit (cooling mode)
  • Dry lamp Dry lamp lit (dry mode)
  • EE Memory chip fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Kinghome KM09-12-18HEDI service manual, sec. 7.8 compulsory defrosting function; Kinghome KM09-12-18-24HT1DI service manual, sec. 6.2 (8) compulsory defrosting function. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.