KeepRite · Heat pump

Forced defrost pins Force a defrost cycle / skip the 5-minute delay

Menu / mode display KeepRite *SA/*SH Single-Stage CommunicatingKeepRite *CA/*CH Two-Stage Communicating

What the display is showing

The heat pump board has a 2-pin header marked FORCED DEFROST. Shorting it for 5 seconds on a non-communicating system starts a defrost (communicating systems start it from the wall control). If the coil is at 32 F or colder and outdoor air is under 50 F a full defrost runs; otherwise only a short 30-second defrost. A quick short and release also skips the 5-minute start delay.

Applies to: Communicating *SA/*SH and *CA/*CH heat pump outdoor boards

What to do

  1. Make sure the system is running a heating call.
  2. Short the two FORCED DEFROST pins with a screwdriver for 5 seconds, then release.
  3. To skip only the 5-minute start delay, short the pins briefly and release.
  4. Quiet Shift compressor on/off delays are included in a forced defrost when enabled.

Models that show this code

11 models in KeepRite *SA/*SH Single-Stage Communicating, KeepRite *CA/*CH Two-Stage Communicating

*CH624*CH636*CH648*CH660*CH924*CH936*CH948*CH960*SH4*SH5*SH6

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: KeepRite ICP split A-C + HP (R-410A & R-22) Application Guideline and Service Manual 421 08 5400 04, Forced Defrost, p.44 and p.57. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.