KeepRite · Heat pump
Fan delay defeat toggle Switch the post-defrost outdoor fan delay off or on
What the display is showing
Normally the outdoor fan stays off 20 seconds after defrost ends so the heat from the coil is picked up and less steam cloud forms. Shorting the forced-defrost pins for more than 15 seconds while the board is idle (amber LED solid) toggles this delay. The setting is kept through power loss.
Applies to: *CA/*CH two-stage communicating heat pump boards
What to do
- With the unit in standby (amber LED on solid), short the FORCED DEFROST pins for more than 15 seconds.
- The LED starts flashing when the toggle has taken place: 4 flashes = delay defeated, 3 flashes = 20 s delay active.
- Remove the short. The code stays up until the short is removed and for about 5 seconds after.
- If you got the wrong state, repeat the toggle.
Models that show this code
8 models in KeepRite *CA/*CH Two-Stage Communicating
Other codes on the same units
- Amber 2 flashes High stage running (normal)
- Amber 3 flashes Outdoor fan delay after defrost is on (20 s)
- Amber 4 flashes Outdoor fan delay after defrost is defeated
- Amber 5 flashes Brown-out protection turned off (user setting)
- Amber 6 flashes Brown-out protection active (user setting)
- Amber LED on solid Standby - no call (communicating)
- Brown-out defeat toggle Turn 230 V brown-out protection off or on
- Forced defrost pins Force a defrost cycle / skip the 5-minute delay
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: KeepRite ICP split A-C + HP (R-410A & R-22) Application Guideline and Service Manual 421 08 5400 04, Defrost / fan delay defeat, p.56-57. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.