KeepRite · Heat pump
Brown-out defeat toggle Turn 230 V brown-out protection off or on
What the display is showing
Service step on the two-stage communicating outdoor board: shorting the forced-defrost pins at power-up, with the outdoor air and coil sensors unplugged, flips the brown-out protection setting. The new setting is remembered through power cycles.
Applies to: *CA/*CH two-stage communicating outdoor boards
What to do
- Power the unit down.
- Unplug the OAT and OCT sensor connector and short the two FORCED DEFROST pins.
- Power the unit up and keep the short on for at least 3 seconds.
- Amber flashes 6 = protection active, 5 = protection off. Repeat once if you land on the wrong state.
- Power down, plug the sensors back in and remove the short.
Models that show this code
8 models in KeepRite *CA/*CH Two-Stage Communicating
Other codes on the same units
- Amber 2 flashes High stage running (normal)
- Amber 3 flashes Outdoor fan delay after defrost is on (20 s)
- Amber 4 flashes Outdoor fan delay after defrost is defeated
- Amber 5 flashes Brown-out protection turned off (user setting)
- Amber 6 flashes Brown-out protection active (user setting)
- Amber LED on solid Standby - no call (communicating)
- Fan delay defeat toggle Switch the post-defrost outdoor fan delay off or on
- Forced defrost pins Force a defrost cycle / skip the 5-minute delay
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: KeepRite ICP split A-C + HP (R-410A & R-22) Application Guideline and Service Manual 421 08 5400 04, Brown-Out Protection Defeated, p.57. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.