KeepRite · Heat pump

Brown-out defeat toggle Turn 230 V brown-out protection off or on

Menu / mode display KeepRite *CA/*CH Two-Stage Communicating

What the display is showing

Service step on the two-stage communicating outdoor board: shorting the forced-defrost pins at power-up, with the outdoor air and coil sensors unplugged, flips the brown-out protection setting. The new setting is remembered through power cycles.

Applies to: *CA/*CH two-stage communicating outdoor boards

What to do

  1. Power the unit down.
  2. Unplug the OAT and OCT sensor connector and short the two FORCED DEFROST pins.
  3. Power the unit up and keep the short on for at least 3 seconds.
  4. Amber flashes 6 = protection active, 5 = protection off. Repeat once if you land on the wrong state.
  5. Power down, plug the sensors back in and remove the short.

Models that show this code

8 models in KeepRite *CA/*CH Two-Stage Communicating

*CH624*CH636*CH648*CH660*CH924*CH936*CH948*CH960

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: KeepRite ICP split A-C + HP (R-410A & R-22) Application Guideline and Service Manual 421 08 5400 04, Brown-Out Protection Defeated, p.57. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.