KeepRite · Heat pump
83 Low pressure lockout
What the control is telling you
Low-pressure switch tripped on 3 cycles in a row. Locked out 4 hours or until 24 V is cycled.
Applies to: KeepRite *SA5/*SA6 AC and *SH4/*SH5/*SH6 HP single-stage communicating; *CA7/*CA9 AC and *CH6/*CH9 HP two-stage communicating
Likely causes
- See code 32
Test and repair steps
- Fix the low-pressure cause (charge, airflow).
- Cycle 24 V to clear.
Models that show this code
11 models in KeepRite *SA/*SH Single-Stage Communicating, KeepRite *CA/*CH Two-Stage Communicating
Other codes on the same units
- 73 Contactor stuck closed
- 74 No 230 V at compressor
- 81 Low stage thermal lockout
- 82 Thermal lockout (two-stage: high stage)
- 84 High pressure lockout
- Amber 1 flash Running - cooling / low stage (normal)
- Amber 2 flashes High stage running (normal)
- Amber 3 flashes Outdoor fan delay after defrost is on (20 s)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: KeepRite/ICP C4A3/H4A3/T4A3/CXA6 Installation Instructions 421 01 5103 05, Table 1 Status Codes, p.17; KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Table 13 Status Codes (single-stage); KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Table 17 Troubleshooting (two-stage). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.