KeepRite · Heat pump

82 Thermal lockout (two-stage: high stage)

High severity KeepRite *SA/*SH Single-Stage CommunicatingKeepRite *CA/*CH Two-Stage Communicating

What the control is telling you

Thermal cutout happened on 3 cycles in a row. The unit (two-stage: high stage) is locked out for 4 hours or until 24 V is cycled.

Applies to: KeepRite *SA5/*SA6 AC and *SH4/*SH5/*SH6 HP single-stage communicating; *CA7/*CA9 AC and *CH6/*CH9 HP two-stage communicating

Likely causes

  • Repeated compressor overload trips - see code 72

Test and repair steps

  1. Find and fix the cause of the code 72 trips first.
  2. Cycle 24 V to clear the lockout.

Models that show this code

11 models in KeepRite *SA/*SH Single-Stage Communicating, KeepRite *CA/*CH Two-Stage Communicating

*CH624*CH636*CH648*CH660*CH924*CH936*CH948*CH960*SH4*SH5*SH6

Other codes on the same units

  • 72 Compressor thermal cutout (two-stage: high stage)
  • 73 Contactor stuck closed
  • 74 No 230 V at compressor
  • 81 Low stage thermal lockout
  • 83 Low pressure lockout
  • 84 High pressure lockout
  • Amber 1 flash Running - cooling / low stage (normal)
  • Amber 2 flashes High stage running (normal)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: KeepRite/ICP C4A3/H4A3/T4A3/CXA6 Installation Instructions 421 01 5103 05, Table 1 Status Codes, p.17; KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Table 13 Status Codes (single-stage); KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Table 17 Troubleshooting (two-stage). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.