Gree · Heat pump

n7 Running parameter query

Menu / mode display Gree GMV6 Mini VRF

What the display is showing

n7 shows live running parameters of a chosen outdoor module on the display, as a two-digit parameter code and its value. The list is: 01 outdoor ambient, 02 compressor 1 frequency, 03 compressor 2 frequency, 04 outdoor fan frequency, 05 module high pressure, 06 module low pressure, 07 to 12 discharge temperatures of compressors 1 to 6, 13 compressor 3 frequency, 14 to 19 compressor currents, 21 to 24 drive module temperatures, 25 to 27 outdoor heating EEV 1, EEV 2 and subcooler EEV, 28 defrost temperature, 29 subcooler liquid outlet, 30 accumulator outlet, 31 oil return, 32 condenser inlet pipe, 33 condenser outlet pipe. Outdoor ambient is shown first.

Applies to: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V..WL/C-T(U))

What to do

  1. Hold SW2 on the master for over 5 seconds, select n7 and confirm with SW3.
  2. Pick the module with SW1 and SW2 and confirm with SW3.
  3. Pick the parameter code with SW1 and SW2.
  4. Four-digit temperatures show as two pairs, for example 01 then 15 for 115 degrees; a negative reading is introduced by nE.

Models that show this code

3 models in Gree GMV6 Mini VRF

GMV-V36WL/C-T(U)GMV-V48WL/C-T(U)GMV-V60WL/C-T(U)

Other codes on the same units

  • n0 Auto energy saving (menu)
  • n1 Defrost cycle K1 setting
  • n3 Forced defrost (menu)
  • n4 Maximum output limit (forced energy saving)
  • n5 Indoor engineering number offset
  • n6 Fault history query
  • n8 Indoor engineering number query
  • n9 Online indoor unit count

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V36-48-60WL-C-T(U)) service.pdf - section 4.2.4.2 and Chapter 3 Faults, 4.1 Error Indication. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.