Gree · Heat pump

n5 Indoor engineering number offset

Menu / mode display Gree GMV6 Mini VRF

What the display is showing

n5 is the outdoor-board menu entry that shifts indoor unit engineering numbers so two systems on one central controller do not clash. Use it only on the master system, the one with SA2 centralized-control address 0000x. After SW3 is pressed n5 goes steady and the system returns to normal after 10 seconds.

Applies to: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V..WL/C-T(U))

What to do

  1. Open the function menu power the system, then hold SW1 on the master outdoor board for over 5 seconds.
  2. Pick the function with SW1 (up) and SW2 (down), confirm with SW3.
  3. SW4 steps back or exits; with no key pressed for 5 minutes the board leaves the menu by itself.
  4. Select n5 (00 flashes) and press SW3 on the master system.

Models that show this code

3 models in Gree GMV6 Mini VRF

GMV-V36WL/C-T(U)GMV-V48WL/C-T(U)GMV-V60WL/C-T(U)

Other codes on the same units

  • n0 Auto energy saving (menu)
  • n1 Defrost cycle K1 setting
  • n3 Forced defrost (menu)
  • n4 Maximum output limit (forced energy saving)
  • n6 Fault history query
  • n7 Running parameter query
  • n8 Indoor engineering number query
  • n9 Online indoor unit count

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V36-48-60WL-C-T(U)) service.pdf - section 4.2.3.9 and Chapter 3 Faults, 4.1 Error Indication. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.