Gree · Heat pump
n3 Forced defrost (menu)
What the display is showing
n3 is the outdoor-board menu entry for forcing a defrost during maintenance. After entry 00 flashes, then SW3 makes n3 go steady. The system leaves the forced defrost on its own when the normal exit conditions are met and then returns to normal control.
Applies to: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V..WL/C-T(U))
What to do
- Open the function menu power the system, then hold SW1 on the master outdoor board for over 5 seconds.
- Pick the function with SW1 (up) and SW2 (down), confirm with SW3.
- SW4 steps back or exits; with no key pressed for 5 minutes the board leaves the menu by itself.
- Select n3 (00 flashes) and press SW3; n3 goes steady.
Models that show this code
3 models in Gree GMV6 Mini VRF
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V36-48-60WL-C-T(U)) service.pdf - section 4.2.3.7 and Chapter 3 Faults, 4.1 Error Indication. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.