Gree · Heat pump

n6 Fault history query

Menu / mode display Gree GMV6 Mini VRF

What the display is showing

n6 opens the history of the last five faults. LED1 cycles through the fault code and module address one at a time at 1 second intervals, and 00 means no more entries. Holding SW3 for over 5 seconds clears the stored history.

Applies to: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V..WL/C-T(U))

What to do

  1. Hold SW2 on the master for over 5 seconds to open the query menu.
  2. Select n6 with SW1 and SW2, confirm with SW3.
  3. Step through entries with SW1 and SW2; 00 ends the list.
  4. Hold SW3 for over 5 seconds to clear the history.

Models that show this code

3 models in Gree GMV6 Mini VRF

GMV-V36WL/C-T(U)GMV-V48WL/C-T(U)GMV-V60WL/C-T(U)

Other codes on the same units

  • n0 Auto energy saving (menu)
  • n1 Defrost cycle K1 setting
  • n3 Forced defrost (menu)
  • n4 Maximum output limit (forced energy saving)
  • n5 Indoor engineering number offset
  • n7 Running parameter query
  • n8 Indoor engineering number query
  • n9 Online indoor unit count

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V36-48-60WL-C-T(U)) service.pdf - section 4.2.4.1 and Chapter 3 Faults, 4.1 Error Indication. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.