Gree · Heat pump
Ld Compressor phase loss
What the control is telling you
The compressor drive found one phase open. It retries after 1 min; after 6 tries it needs a power reset.
Applies to: Gree Multi21+ 18-24k multi-zone (MULTI..HP230V1CO)
Likely causes
- Compressor U/V/W wire loose or broken
- Compressor winding open
- Board fault
Test and repair steps
- Warning: Kill power and let the outdoor board capacitors bleed down (about 20 min, or meter the DC bus below 20 V) before touching the inverter board.
- Check compressor wiring and order.
- Measure winding resistance.
- Replace the compressor or outdoor board as found.
Models that show this code
2 models in Gree Multi21+
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Gree Multi21+ multi-zone 18-24k (MULTI18-24HP230V1CO) service.pdf - section 9.1 Malfunction status sheet / 9.2 Malfunction Checking and Elimination. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.