Gree · Heat pump
PU DC bus capacitor charging fault
What the control is telling you
The outdoor board cannot charge its DC bus capacitor to normal voltage.
Applies to: Gree Sapphire 9-24k (SAP..HP230V1A), Livo GEN4 30-36k (4LIV..HP230V1A), Vireo GEN3 9-24k (3VIR..HP115/230V1A), Multi21+ 18-24k multi-zone (MULTI..HP230V1CO)
Likely causes
- Supply voltage outside 180-260 VAC
- Reactor (L) wiring loose or reactor failed
- Outdoor board (AP1) fault
Test and repair steps
- Measure the supply at XT L-N (normal range 210-240 VAC, limit 180-260 VAC) and correct it if out of range.
- Warning: Kill power and let the outdoor board capacitors bleed down (about 20 min, or meter the DC bus below 20 V) before touching the inverter board.
- Check the reactor connections and test the reactor.
- Run the unit 1 minute and measure across the electrolytic capacitor; if it stays below 200 V with good supply and reactor, replace AP1.
Models that show this code
14 models in Gree Sapphire, Gree Livo GEN4, Gree Vireo GEN3, Gree Multi21+
Other codes on the same units
- Outdoor comm light blinking Outdoor communication light blinking (normal)
- PH DC bus voltage too high
- PL DC bus voltage too low
- SE Energy-saving mode active
- Temp display select Indoor display shows set, room or outdoor temperature
- Turbo icon Turbo mode active
- WiFi icon WiFi function on
- X-FAN icon X-FAN (coil dry-off) active
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Gree Sapphire 9-12k (SAP09-12HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Sapphire 18-24k (SAP18-24HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Livo GEN4 30-36k (4LIV30-36HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Vireo GEN3 9-24k (3VIR..HP115-230V1A) service GREE_VIREOGEN3_SERVICE_090921.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Multi21+ multi-zone 18-24k (MULTI18-24HP230V1CO) service.pdf - section 9.1 Malfunction status sheet / 9.2 Malfunction Checking and Elimination. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.