Gree · Heat pump

Lb Group control: units from different systems

Low severity Gree GMV6 Mini VRF

What the control is telling you

One controller is connected to indoor units of separate systems.

Applies to: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V..WL/C-T(U))

Likely causes

  • Controller wiring

Test and repair steps

  1. Wire the controller to one system only.

Models that show this code

3 models in Gree GMV6 Mini VRF

GMV-V36WL/C-T(U)GMV-V48WL/C-T(U)GMV-V60WL/C-T(U)

Other codes on the same units

  • JA Abnormal pressure protection
  • JL High pressure too low
  • LA Group control: indoor series mismatch
  • LJ Indoor function DIP setting wrong
  • LU PG fan motor zero-crossing fault
  • PA Compressor drive memory chip fault
  • PC Compressor drive current sensing fault
  • PE Inverter compressor phase loss

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V36-48-60WL-C-T(U)) service.pdf - section Chapter 3 Faults, 4.1 Error Indication. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.