Gree · Heat pump
PE Inverter compressor phase loss
What the control is telling you
Compressor drive fault: inverter compressor phase loss.
Applies to: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V..WL/C-T(U))
Likely causes
- Compressor winding fault
- Poor refrigerant flow or dirty coils/filters
- Supply voltage problem
- Drive / main board fault
Test and repair steps
- Warning: Turn off power and wait for the board to discharge before testing.
- Measure compressor windings equal resistance between terminals and open to ground.
- Check refrigerant flow and clean filters, coils and blower wheels.
- Check 208/230 VAC supply.
- Power off 15 min and restart; if the code repeats after 3 tries, replace the outdoor main board (or the compressor if windings fail).
Models that show this code
3 models in Gree GMV6 Mini VRF
Other codes on the same units
- PA Compressor drive memory chip fault
- PC Compressor drive current sensing fault
- PF Compressor drive charging circuit fault
- PH DC bus voltage too high
- PJ Inverter compressor failed to start
- PL DC bus voltage too low
- PP Inverter compressor AC current protection
- Power LED Main board and drive board power LEDs on
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V36-48-60WL-C-T(U)) service.pdf - section Chapter 3 Faults, 4.1 Error Indication. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.