Gree · Heat pump

dd Wiring/EEV check running (status)

Low severity Gree Multi21+

What the control is telling you

Not a fault. The outdoor unit is checking zone wiring and expansion valves.

Applies to: Gree Multi21+ 18-24k multi-zone (MULTI..HP230V1CO)

Test and repair steps

  1. Wait for the check to finish; if dn follows, fix the zone wiring or EEV.

Models that show this code

2 models in Gree Multi21+

MULTI18HP230V1COMULTI24HP230V1CO

Other codes on the same units

  • LC Compressor failed to start
  • LP Indoor and outdoor units do not match
  • Ld Compressor phase loss
  • Light x6 View stored malfunction code on remote
  • PH DC bus voltage too high
  • PL DC bus voltage too low
  • PU DC bus capacitor charging fault
  • dn Wrong interconnect wiring or EEV fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Gree Multi21+ multi-zone 18-24k (MULTI18-24HP230V1CO) service.pdf - section 9.1 Malfunction status sheet / 9.2 Malfunction Checking and Elimination. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.