Goodman · Furnace
EE7 Igniter circuit fault or poor ground
What the control is telling you
The control found a problem in the igniter circuit or in the unit ground, so the furnace will not run. Check the igniter wiring and the ground path first.
Applies to: GMVC96, GCVC96, AMVC96, ACVC96 (*BA, ComfortBridge)
Likely causes
- Igniter plug loose or wired wrong
- Shorted igniter
- Poor unit ground
- Igniter relay fault on the control
Test and repair steps
- Turn off power before touching wiring or the board.
- Check the wiring from the control to the igniter and fix any loose pin or bad connection.
- Measure the igniter cold a good 120 V silicon nitride igniter reads about 37 to 68 ohms. Replace it if it is shorted or out of range. Handle it by the mounting only.
- Check the unit ground wire back to the panel.
- Check the igniter output at the control. Replace the control only if the output is missing with good wiring and a good igniter.
Settings for these units
- Normal status displays (7-segment) · Goodman/Amana GM9S96/AM9S96
- Normal status displays (7-segment) · Goodman/Amana GM9S80/AM9S80
- Normal status displays (7-segment) · Goodman/Amana GM9C96/AM9C96
- Minimum recommended filter size · Goodman/Amana GM9C96/AM9C96
Models that show this code
16 models in Goodman/Amana *MVC96 (34.5 in. chassis)
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman Service and Troubleshooting ACVC96*BA/AMVC96*BA/GCVC96*BA/GMVC96*BA , Alarm Code Table p.56 / Troubleshooting Chart p.61. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.