Fujitsu · Heat pump

MANUAL AUTO 10 s Start test run / forced cooling from the indoor unit

Menu / mode display Fujitsu wall-mounted 7-15 (NA ASU/AOU type)Fujitsu multi-zone outdoor 18/24 type

What the display is showing

Keeping the indoor unit's MANUAL AUTO button pressed longer than 10 seconds starts a forced cooling or test run when the remote is lost or the outdoor unit will not start on room temperature. The OPERATION and TIMER lamps then flash together. A short press of MANUAL AUTO is enough to stop it. Forced cooling will not start if the button is released before 10 seconds.

Applies to: Fujitsu ductless heat pumps: Fujitsu wall-mounted 7-15 (NA ASU/AOU type); Fujitsu ductless heat pumps: Fujitsu multi-zone outdoor 18/24 type (18 type 2-zone, 24 type 3-zone)

What to do

  1. Keep MANUAL AUTO pressed longer than 10 seconds.
  2. Watch for the OPERATION and TIMER lamps flashing together.
  3. In the wall unit the heating test run follows about three minutes later when HEAT is chosen on the remote.
  4. Stop with the remote START/STOP key, or press MANUAL AUTO briefly.

Settings for these units

Operating range and service space · Fujitsu multi-zone outdoor 18/24 type

ItemValue
Cooling outdoor range14 to 115 F DB
Heating outdoor range5 to 75 F DB
Cooling indoor range65 to 90 F DB
Heating indoor range60 to 88 F DB
Rear (open top, rear wall only)4 in. or more
Rear + sides4 in. rear, 10 in. sides
Front wall only24 in. or more
Between side-by-side units10 in. or more
Base height2 in. or more above floor

Unit tilt no more than 3 degrees and never toward the compressor side.

Below 32 F outdoor do not fit the drain pipe/caps (freezing).

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Fujitsu Wall-mounted 7-9-12-15 (North American trilingual, UTY-RNNUM remotes; e.g. ASU9-12-15 RLF1-RLS familie.pdf - section 12 Test run; Fujitsu Outdoor unit 18-24 type (North American trilingual) installation P-N 9374747160.pdf - section 9 Pump down operation. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.