Fujitsu · Heat pump

Error memory recall Show the stored error on the indoor lamps

Menu / mode display Fujitsu wall-mounted KMCG (ASEH-AOEH 07-14)

What the display is showing

The indoor unit stores the last error in memory even through a power cut, and a newer error replaces the older one. The stored error can be read on the OPERATION, TIMER and ECONOMY lamps during the 3-minute start-up wait (2 minutes 20 seconds after power is applied). If nothing is stored the unit shows its TEST RUN display instead. The memory clears after 2 hours of fault-free running or by pressing MANUAL AUTO while it is displayed.

Applies to: Fujitsu ductless heat pumps: Fujitsu wall-mounted KMCG (ASEH07-14KMCG / AOEH07-14KMCG)

What to do

  1. Stop the unit, remove power, then switch power back on.
  2. During the 2 minute 20 second start-up wait, run the unit and press TEST RUN on the remote, or keep MANUAL AUTO pressed on the indoor unit for at least 10 seconds.
  3. Read the lamp flashes against the error table.
  4. To erase it press MANUAL AUTO while the memory is shown (short beep for about 3 seconds).

Settings for these units

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Fujitsu Wall-mounted KMCG (ASEH-AOEH 07-14) - Fujitsu UK; same error-code scheme as NA ASU-AOU units service S.pdf - section 03 Troubleshooting, 1-1 and 1-2 error memory. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.