E4 E4 subcode 02: heat source unit low refrigerant or stop valve closed
What the control is telling you
Heat source unit reports refrigerant shortage. The stop valve is closed or the charge is too low.
Applies to: Heat source unit
Likely causes
- Heat source unit stop valve is closed
- Insufficient refrigerant charge
Test and repair steps
- Open the heat source unit stop valve.
- Confirm the additional refrigerant charge was done.
- Recalculate the additional charge using the charge calculation in the manual and add the correct amount.
Other codes on the same units
- 80 Thermistor connector X17A disconnected (cascade)
- 81 Thermistor connector X18A disconnected (cascade)
- A6 Water not flowing in cascade unit
- E3 E3 subcode 01: cascade unit HPS connector unplugged
- E9 E9 subcode 01: cascade unit X23A valve coil connector unplugged
- F3 F3 subcode 01: cascade unit low refrigerant
- H9 H9 subcode 02: heat source X18A thermistor disconnected
- J3 J3 subcodes 16 to 19: cascade unit X29A thermistor disconnected
Sequence of operation
What the unit does around this code, step by step.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Mega-Q installation manual, p. 48. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.