Daikin · Water heater
A6 Water not flowing in cascade unit
What the control is telling you
Water is not flowing through the cascade unit. Also the A7P connector X40A or X2A (or relay connectors X2A or X3A) may be disconnected.
Applies to: Cascade unit
Likely causes
- Gate valve before or after cascade unit closed
- Strainer clogged
- Water supply pump not running
- Air trapped in water piping
- Inlet pressure out of range
- On-site piping frozen
- X40A or X2A connector disconnected on A7P or relay connector
Test and repair steps
- Confirm the gate valves before and after the cascade unit are open.
- Clean the strainer if clogged.
- Check the water supply pump is operating normally.
- Release air from the water piping.
- Confirm inlet pressure is within the piping work range.
- Check that on-site piping is not frozen.
- Reconnect X40A or X2A (or relay connector X2A or X3A) per the wiring diagram.
Other codes on the same units
- 42 Connector X3A disconnected (cascade)
- 80 Thermistor connector X17A disconnected (cascade)
- 81 Thermistor connector X18A disconnected (cascade)
- E3 E3 subcode 01: cascade unit HPS connector unplugged
- E4 E4 subcode 02: heat source unit low refrigerant or stop valve closed
- E9 E9 subcode 01: cascade unit X23A valve coil connector unplugged
- F3 F3 subcode 01: cascade unit low refrigerant
- H9 H9 subcode 02: heat source X18A thermistor disconnected
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin Mega-Q installation manual, p. 50. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.