Daikin · Heat pump
Green Rx LED off Network: no power or no communication
What the control is telling you
Green receive LED (outdoor board H2P, indoor board H3P) is off.
Applies to: DH6VS***1*A*, DH7VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)
Likely causes
- No power to the unit
- Open fuse
- Communication error
Test and repair steps
- Check breakers and fuses. Reset or replace.
- Press LEARN about 5 seconds to reset the network.
- Check the terminal 1 / terminal 2 communication wires.
- Look for a short in the low voltage wiring.
Models that show this code
11 models in Daikin FIT DH6VS/DH7VSA
Other codes on the same units
- Ed1 Bad shared or network data
- Ed2 Airflow needed is more than the indoor unit can give
- Ed3 Shared data does not match the hardware
- Ed4 Memory card data rejected
- Green Rx LED 1 steady flash Network: no network found
- Green Rx LED on solid Network: terminal 1 / 2 miswired
- Red comm LED 1 flash Network: communications failure
- Red comm LED 2 flashes Network: out-of-box reset
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin 3P761829-1B FIT outdoor unit installation & service reference, Network Troubleshooting p.47 (printed page). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.