Daikin · Heat pump
Ed2 Airflow needed is more than the indoor unit can give
What the control is telling you
Thermostat shows D2, outdoor board display shows Ed2. The outdoor unit asks for more airflow than the indoor unit can deliver, or an indoor unit without an EEV is connected.
Applies to: DH6VS***1*A*, DH7VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)
Likely causes
- Indoor and outdoor units not a listed match
- Shared data wrong for the system or missing settings
- Loose communication wiring to the indoor unit
- Airflow trim setting out of range
Test and repair steps
- Check the indoor/outdoor match against the rating list.
- Check the shared data matches the model. Load it again if needed.
- Check communication and power wiring at the indoor unit.
- Check the indoor CFM trim setting in the thermostat and bring it back into range.
Models that show this code
11 models in Daikin FIT DH6VS/DH7VSA
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.46 (printed page). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.