Daikin · Heat pump
E34 High current detected
What the control is telling you
Thermostat shows 34, outdoor board display shows E34. The control board saw high current.
Applies to: DH6VS***1*A*, DH7VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)
Likely causes
- Current spike on the power supply
- Stop valve not fully open
- Lost phase on the compressor wires
- Bad control board
- Bad compressor
Test and repair steps
- Kill power at the disconnect before opening the control box or touching wiring.
- Check the power supply for in-rush current at start-up and while running.
- Open both stop valves all the way.
- Check the compressor wires between the board and the compressor.
- Check the compressor.
- Replace the control board if everything else is good.
Models that show this code
11 models in Daikin FIT DH6VS/DH7VSA
Other codes on the same units
- E28 Outdoor coil temperature sensor out of range
- E29 Liquid temperature sensor out of range
- E30 Control board may need replacing
- E32 Outdoor control board overheating (critical)
- E35 High current, possible short circuit
- E36 Abnormal start-up
- E37 Control board may need replacing (fan motor link)
- E38 Compressor voltage problem
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.44 (printed page). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.