Daikin · Heat pump
E32 Outdoor control board overheating (critical)
What the control is telling you
Thermostat shows 32, outdoor board display shows E32. The outdoor control board keeps running too hot.
Applies to: DH6VS***1*A*, DH7VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)
Likely causes
- Outdoor temperature too high
- Stop valve not fully open
- Board cooling bracket screws missing or loose (3.5-5.0 ton FIT and 3.0-4.0 ton Enhanced Capacity/High Efficiency FIT only)
- Missing or poor thermal grease between the cooling pipe and the board cooling bracket (3.5-5.0 ton FIT and 3.0-4.0 ton Enhanced Capacity/High Efficiency FIT only)
- Little or no refrigerant flow through the board cooling circuit, from a restriction or low charge (3.5-5.0 ton FIT and 3.0-4.0 ton Enhanced Capacity/High Efficiency FIT only)
Test and repair steps
- Kill power at the disconnect before opening the control box or touching wiring.
- If it is very hot outside, cycle power and try again when the temperature is back in the unit's range.
- Open both stop valves all the way.
- On the larger units listed, check the cooling bracket screws and the thermal grease on the board cooling plate.
- Look for a restriction in the lines.
- Check the charge and adjust if needed.
Models that show this code
11 models in Daikin FIT DH6VS/DH7VSA
Other codes on the same units
- E27 Outdoor coil defrost sensor out of range
- E28 Outdoor coil temperature sensor out of range
- E29 Liquid temperature sensor out of range
- E30 Control board may need replacing
- E34 High current detected
- E35 High current, possible short circuit
- E36 Abnormal start-up
- E37 Control board may need replacing (fan motor link)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.44 (printed page). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.