Daikin · Heat pump
33 Outdoor control board overheating (minor)
What the control is telling you
The thermostat shows 33; the board shows nothing. The board has run hot several times but the control lets the unit keep going.
Applies to: DH6VS***1*A*, DH7VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)
Likely causes
- Outdoor temperature too high
- Stop valve not fully open
- Board cooling bracket screws missing or loose (3.5-5.0 ton FIT and 3.0-4.0 ton Enhanced Capacity/High Efficiency FIT only)
- Missing or poor thermal grease between the cooling pipe and the board cooling bracket (3.5-5.0 ton FIT and 3.0-4.0 ton Enhanced Capacity/High Efficiency FIT only)
- Little or no refrigerant flow through the board cooling circuit, from a restriction or low charge (3.5-5.0 ton FIT and 3.0-4.0 ton Enhanced Capacity/High Efficiency FIT only)
Test and repair steps
- Kill power at the disconnect before opening the control box or touching wiring.
- If it is very hot outside, cycle power and try again when the temperature is back in the unit's range.
- Open both stop valves all the way.
- On the larger units listed, check the cooling bracket screws and the thermal grease on the board cooling plate.
- Look for a restriction in the lines.
- Check the charge and adjust if needed.
Models that show this code
11 models in Daikin FIT DH6VS/DH7VSA
Other codes on the same units
- 14 Repeated high pressure faults (minor)
- 16 Repeated low pressure faults (minor)
- 52 Repeated compressor faults (minor)
- 53 Repeated outdoor fan / board faults (minor)
- 54 Repeated low discharge superheat faults (minor)
- 55 Repeated high discharge temperature faults (minor)
- 57 Sweating on the board cooling loop
- E11 System start-up test not done
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.44 (printed page). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.