Daikin · Heat pump

14 Repeated high pressure faults (minor)

Medium severity Daikin FIT DH6VS/DH7VSA

What the control is telling you

The thermostat shows 14; the board shows nothing. The unit has had several high pressure trips but the control lets it keep running. Something is still wrong and should be found.

Applies to: DH6VS***1*A*, DH7VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)

Likely causes

  • Stop valve not fully open
  • Dirty or blocked outdoor coil, or a restriction in the lines
  • Too much refrigerant
  • Outdoor fan not running
  • High pressure switch not working
  • Bad indoor or outdoor EEV, or its coil
  • Bad control board

Test and repair steps

  1. Kill power at the disconnect before opening the control box or touching wiring.
  2. Clean the outdoor coil and look for a restriction in the lines.
  3. Open both stop valves all the way.
  4. Check the charge. Recover refrigerant if the unit is overcharged.
  5. Make sure the outdoor fan turns. Check the fan motor and its wiring.
  6. Check the high pressure switch.
  7. Check the indoor and outdoor EEV and their coils. Replace the bad part.
  8. If everything else checks out, replace the control board.

Models that show this code

11 models in Daikin FIT DH6VS/DH7VSA

DH6VS*181DH6VS*241DH6VS*301DH6VS*361DH6VS*421DH6VS*481DH6VS*601DH7VSA2410DH7VSA3610DH7VSA4210DH7VSA4810

Other codes on the same units

  • 16 Repeated low pressure faults (minor)
  • 33 Outdoor control board overheating (minor)
  • 52 Repeated compressor faults (minor)
  • 53 Repeated outdoor fan / board faults (minor)
  • 54 Repeated low discharge superheat faults (minor)
  • 55 Repeated high discharge temperature faults (minor)
  • 57 Sweating on the board cooling loop
  • E11 System start-up test not done

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.43 (printed page). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.