Daikin · Air conditioner

CoreSense solid red CoreSense: solid red TRIP

High severity Daikin R-32 DC3S/DC4S/DC5S

What the control is telling you

Solid red TRIP LED: the thermostat is calling (Y is there) but the compressor is not running.

Applies to: DC3SQN, DC4SQA, DC4SEA, DC5SEA (single stage R-32 condensing units with CoreSense module)

Likely causes

  • Compressor internal protector open (check head pressure and compressor voltage)
  • Outdoor disconnect open
  • Compressor breaker or fuses open
  • Broken wire or loose connector
  • High pressure switch open (if fitted)
  • Compressor contactor failed open

Test and repair steps

  1. Kill power at the disconnect before working in the unit. There can be more than one power source.
  2. Check the disconnect, breaker and fuses.
  3. Check the contactor and wiring to the compressor for a broken wire or loose plug.
  4. Check the high pressure switch if the unit has one.
  5. If the compressor protector is open, check head pressure and compressor supply voltage, and let it cool and reset.

Models that show this code

4 models in Daikin R-32 DC3S/DC4S/DC5S

DC3SQN**10AADC4SEA**10AADC4SQA**10AADC5SEA**10AA

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Diagnostics Table: CoreSense Module p.20-21 and Table 1 Quick Reference p.22. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.