Daikin · Air conditioner
CoreSense 4 CoreSense: 4 flashes, locked rotor (yellow alert / red lock)
What the control is telling you
Code 4: the compressor trips within 12 seconds of starting and does not start again within 35 seconds. Yellow 4 flashes = alert. Red 4 flashes with yellow off = locked out after 10 in a row.
Applies to: DC3SQN, DC4SQA, DC4SEA, DC5SEA (single stage R-32 condensing units with CoreSense module)
Likely causes
- Run capacitor failed
- Low line voltage or bad wiring connections
- Too much liquid refrigerant in the compressor
- Seized compressor bearings
Test and repair steps
- Kill power at the disconnect before working in the unit. There can be more than one power source.
- Test the run capacitor. Replace it if it is out of spec.
- Measure line voltage at the disconnect while starting. If it is low there, the utility has to look at it.
- Check the wiring connections.
- Look for liquid refrigerant in the compressor.
- Check the compressor oil level. A seized compressor has to be replaced.
- After the fix, press the module reset to clear a lockout.
Models that show this code
4 models in Daikin R-32 DC3S/DC4S/DC5S
Other codes on the same units
- CoreSense 1 CoreSense: yellow 1 flash, long run time
- CoreSense 2 CoreSense: 2 flashes, pressure trip (yellow alert / red lock)
- CoreSense 3 CoreSense: 3 flashes, short cycling (yellow alert / red lock)
- CoreSense 5 CoreSense: 5 flashes, moderate run trip (yellow alert / red lock)
- CoreSense 9 CoreSense: red 9 flashes, PROT terminal over current
- CoreSense TRIP+ALERT flashing CoreSense: TRIP and ALERT flashing together
- CoreSense solid red CoreSense: solid red TRIP
- CoreSense solid yellow CoreSense: solid yellow RUN
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Diagnostics Table: CoreSense Module p.20-21 and Table 1 Quick Reference p.22. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.