Daikin · Air conditioner

CoreSense 2 CoreSense: 2 flashes, pressure trip (yellow alert / red lock)

High severity Daikin R-32 DC3S/DC4S/DC5S

What the control is telling you

Code 2: the compressor ran 12 seconds to 15 minutes, then tripped for more than 7 minutes (discharge pressure out of limits or overload). Yellow 2 flashes = alert. Red 2 flashes with yellow off = locked out after 4 trips in a row or 10 total.

Applies to: DC3SQN, DC4SQA, DC4SEA, DC5SEA (single stage R-32 condensing units with CoreSense module)

Likely causes

  • Outdoor fan not running: bad fan capacitor, wiring, or a failed or blocked fan motor
  • High head pressure: high pressure switch open, overcharge, or non-condensables
  • Dirty, blocked or damaged outdoor coil

Test and repair steps

  1. Kill power at the disconnect before working in the unit. There can be more than one power source.
  2. Check the outdoor fan capacitor, wiring and plugs, motor and blade.
  3. Check the high pressure switch if the unit has one.
  4. Check the charge. Look for overcharge or non-condensables.
  5. Clean the outdoor coil and clear anything blocking airflow.
  6. After the fix, press the module reset to clear a lockout.

Models that show this code

4 models in Daikin R-32 DC3S/DC4S/DC5S

DC3SQN**10AADC4SEA**10AADC4SQA**10AADC5SEA**10AA

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Diagnostics Table: CoreSense Module p.20-21 and Table 1 Quick Reference p.22. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.