CoreSense 9 CoreSense: red 9 flashes, PROT terminal over current

Medium severity Daikin R-32 DC3S/DC4S/DC5S

What the control is telling you

Red 9 flashes, yellow off: current through the PROT terminal was over 2 A for 40 ms.

Applies to: DC3SQN, DC4SQA, DC4SEA, DC5SEA (single stage R-32 condensing units with CoreSense module)

Likely causes

  • More than 2 A on the PROT (protection output) terminal

Test and repair steps

  1. Kill power at the disconnect before working in the unit. There can be more than one power source.
  2. Check what is wired to the PROT terminal and its wiring for a short or too much load.

Models that show this code

4 models in Daikin R-32 DC3S/DC4S/DC5S

DC3SQN**10AADC4SEA**10AADC4SQA**10AADC5SEA**10AA

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Diagnostics Table: CoreSense Module p.20-21 and Table 1 Quick Reference p.22. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.