Daikin · Air conditioner

52 Repeated compressor faults (minor)

Medium severity Daikin FIT DC6VS/DC9VSA

What the control is telling you

The thermostat shows 52; the board shows nothing. Several compressor faults, but the control lets the unit keep running.

Applies to: DC6VS***1*A*, DC9VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)

Likely causes

  • Stop valve not fully open
  • Lost phase on the compressor wires
  • Compressor motor failure

Test and repair steps

  1. Kill power at the disconnect before opening the control box or touching wiring.
  2. Open both stop valves all the way.
  3. Check the compressor wires between the control board and the compressor. Look for a loose or burnt terminal.
  4. Check the compressor motor. Replace the compressor if it has failed.

Models that show this code

10 models in Daikin FIT DC6VS/DC9VSA

DC6VS*181DC6VS*241DC6VS*301DC6VS*361DC6VS*421DC6VS*481DC6VS*601DC9VSA2410DC9VSA3610DC9VSA4810

Other codes on the same units

  • 14 Repeated high pressure faults (minor)
  • 16 Repeated low pressure faults (minor)
  • 33 Outdoor control board overheating (minor)
  • 53 Repeated outdoor fan / board faults (minor)
  • 54 Repeated low discharge superheat faults (minor)
  • 55 Repeated high discharge temperature faults (minor)
  • 57 Sweating on the board cooling loop
  • E11 System start-up test not done

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.45 (printed page). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.