Daikin · Air conditioner
52 Repeated compressor faults (minor)
What the control is telling you
The thermostat shows 52; the board shows nothing. Several compressor faults, but the control lets the unit keep running.
Applies to: DC6VS***1*A*, DC9VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)
Likely causes
- Stop valve not fully open
- Lost phase on the compressor wires
- Compressor motor failure
Test and repair steps
- Kill power at the disconnect before opening the control box or touching wiring.
- Open both stop valves all the way.
- Check the compressor wires between the control board and the compressor. Look for a loose or burnt terminal.
- Check the compressor motor. Replace the compressor if it has failed.
Models that show this code
10 models in Daikin FIT DC6VS/DC9VSA
Other codes on the same units
- 14 Repeated high pressure faults (minor)
- 16 Repeated low pressure faults (minor)
- 33 Outdoor control board overheating (minor)
- 53 Repeated outdoor fan / board faults (minor)
- 54 Repeated low discharge superheat faults (minor)
- 55 Repeated high discharge temperature faults (minor)
- 57 Sweating on the board cooling loop
- E11 System start-up test not done
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.45 (printed page). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.