Daikin · Air conditioner
54 Repeated low discharge superheat faults (minor)
What the control is telling you
The thermostat shows 54; the board shows nothing. Low discharge superheat several times, but the unit keeps running.
Applies to: DC6VS***1*A*, DC9VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)
Likely causes
- Thermistor bad or not plugged in right
- Bad indoor EEV or its coil (in cooling)
- Bad outdoor EEV or its coil (in heating)
- Bad control board
Test and repair steps
- Kill power at the disconnect before opening the control box or touching wiring.
- Check the thermistor plugs.
- In cooling, check the indoor EEV and its coil. In heating, check the outdoor EEV and its coil.
- Replace the board last.
Models that show this code
10 models in Daikin FIT DC6VS/DC9VSA
Other codes on the same units
- 16 Repeated low pressure faults (minor)
- 33 Outdoor control board overheating (minor)
- 52 Repeated compressor faults (minor)
- 53 Repeated outdoor fan / board faults (minor)
- 55 Repeated high discharge temperature faults (minor)
- 57 Sweating on the board cooling loop
- E11 System start-up test not done
- E12 Control board memory error
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.45 (printed page). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.