Daikin · Air conditioner
14 Repeated high pressure faults (minor)
What the control is telling you
The thermostat shows 14; the board shows nothing. The unit has had several high pressure trips but the control lets it keep running. Something is still wrong and should be found.
Applies to: DC6VS***1*A*, DC9VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)
Likely causes
- Stop valve not fully open
- Dirty or blocked outdoor coil, or a restriction in the lines
- Too much refrigerant
- Outdoor fan not running
- High pressure switch not working
- Bad indoor or outdoor EEV, or its coil
- Bad control board
Test and repair steps
- Kill power at the disconnect before opening the control box or touching wiring.
- Clean the outdoor coil and look for a restriction in the lines.
- Open both stop valves all the way.
- Check the charge. Recover refrigerant if the unit is overcharged.
- Make sure the outdoor fan turns. Check the fan motor and its wiring.
- Check the high pressure switch.
- Check the indoor and outdoor EEV and their coils. Replace the bad part.
- If everything else checks out, replace the control board.
Models that show this code
10 models in Daikin FIT DC6VS/DC9VSA
Other codes on the same units
- 16 Repeated low pressure faults (minor)
- 33 Outdoor control board overheating (minor)
- 52 Repeated compressor faults (minor)
- 53 Repeated outdoor fan / board faults (minor)
- 54 Repeated low discharge superheat faults (minor)
- 55 Repeated high discharge temperature faults (minor)
- 57 Sweating on the board cooling loop
- E11 System start-up test not done
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.43 (printed page). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.