What the control is telling you
The indoor PCB is not getting feedback from the display board.
Applies to: D5FSFAH floor console ductless system, sizes 09K to 16K (indoor unit)
Likely causes
- Communication wire fault
- Indoor PCB fault
- Display board fault
Test and repair steps
- Check the wiring and connections between the indoor PCB and display board.
- If the connections are good, replace the indoor main PCB.
- If the error remains, replace the display board.
- Wait 2 minutes, then restart the unit.
- Make sure all connections are secure before restarting.
Models that show this code
3 models in D5FSFA
Other codes on the same units
- EC 0d Outdoor unit malfunction detected by indoor unit
- EH 06 Indoor PCB and display board communication error
- EH 0b Indoor main board and display board communication error
- EH 3A External fan DC bus voltage too low
- EH 3b External fan DC bus voltage too high
- EH 62 Indoor temperature sensor open or shorted
- EH 65 Indoor temperature sensor open or shorted
- EH 66 Indoor temperature sensor open or shorted
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier D5FSFAH service manual, p. 32. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.